| Acoustic Foam Attenuation | |||||||
|---|---|---|---|---|---|---|---|
| Transmission Loss dB|Frequency (Hz) | 65 | 125 | 250 | 500 | 1000 | 2000 | 4000 |
| 3.5kg/m5 PVC/ Barrier mat | - | 15 | 15 | 17 | 21 | 27 | 30 |
| Duct Size 900 x 600 (12mm foam) | - | 0.2 | 0.6 | 1.7 | 3.7 | 5.3 | 4.5 |
| Duct Size 900 x 600 (25mm foam) | - | 0.2 | 0.8 | 2.9 | 10.8 | 6.9 | 7.2 |
| Duct Size 900 x 600 (50mm foam) | - | 0.8 | 2.9 | 7.2 | 11.0 | 7.1 | 6.2 |
| Duct Size 450 x 600 (25mm foam) | - | 0.4 | 1.0 | 3.3 | 14.1 | 8.3 | 8.9 |
| Duct Size 450 x 600 (50mm foam) | - | 1.6 | 3.1 | 0.92 | 16.6 | 8.8 | 8.6 |
| Duct Size 300 x 600 (25mm foam) | - | 0.6 | 1.4 | 8.7 | 15.1 | 12.0 | 11.4 |
| Duct Size 300 x 600 (50mm foam) | - | 2.6 | 5.4 | 10.5 | 19.5 | 15.1 | 11.6 |